Power Plant

Hydrogen Leak due to Inappropriate Operator Action results in Fire

12:23 PM Tue Nov 2, 2010 -- Anonymous (not verified)

Unit 1 Plant power was stable at 90% following a plant startup. The Auxiliary Operator (AO) performed a pre-job brief with shift management before adding hydrogen to the main generator. While performing the addition, the AO attempted to verify open a half-inch hydrogen addition valve. The AO was unable to move the valve by hand and mistakenly assumed the valve was stuck on its closed seat. The valve is a normally open valve and the procedure step was to verify the valve was, in fact, open. The AO obtained a pipe wrench to assist in freeing the valve off of its "closed" seat.

Hydrogen Leak and Fire at Nuclear Power Plant

12:23 PM Mon Aug 23, 2010 -- Anonymous (not verified)

Severe vibrations caused by broken low-pressure turbine blades damaged the main turbine generator at a nuclear power plant. These vibrations also caused multiple hydrogen leaks at equipment connections to the generator, resulting in hydrogen flames outside of the generator casing that caused minimal damage to the facility. Hydrogen is used to internally cool the plant's electric generators. Water from the fire suppression system and oil released from the turbine lube oil system during the event were contained within the plant, resulting in no impact to the environment.

Hydrogen Leak into Main Generator Stator Cooling Water System Causes Nuclear Plant to Shutdown

11:23 AM Thu Jan 7, 2010 -- Anonymous (not verified)

A previously identified generator hydrogen gas leakage into the stator cooling water system exceeded the predetermined maximum operational allowance and the nuclear plant was shut down from 100 percent power in accordance with plant operating procedures. The leak was identified by monitoring the stator water cooling system detraining tank. Following reactor shut down and generator rotor removal, a small hole was located in the collector end winding area of a slot on the top stator bar.

Hydrogen Leak Through Pinhole Weld Defects in Stator Cooling Water System Forces Nuclear Plant Shutdowns

12:23 PM Mon Oct 5, 2009 -- Anonymous (not verified)

Hydrogen and water leakage in the main generator stator cooling water (SCW) equipment forced two separate shutdowns of a nuclear plant in a three-month period. Manufacturer weld defects on the SCW exciter end ring header are the likely cause for the hydrogen leakage.

Hydrogen Delivery Truck Causes Hydrogen Leak at Fill Station Due to Improperly Stored Hydrogen Fill Line at Departure

12:23 PM Mon Oct 5, 2009 -- Anonymous (not verified)

A hydrogen leak occurred at a plant's hydrogen fill station when a vendor's hydrogen fill truck trailer pulled away after filling and caught an improperly stored hydrogen fill line. The driver of the hydrogen truck trailer did not properly stow the hydrogen fill line after filling and failed to verify that the hydrogen fill line was clear of the trailer prior to departure. As the driver pulled away from the fill station, the hydrogen fill line caught on the trailer and subsequently pulled on the hydrogen fill station's ground storage tubes distribution manifold.

Ruptured CO2 Cylinder Causes Hydrogen Fire

12:23 PM Mon May 12, 2008 -- Anonymous (not verified)

A five-pound CO2 cylinder being stored in a compressed gas storage cage at a power plant failed catastrophically and became a missile. The cylinder destroyed the storage cage, then struck one of six stationary hydrogen storage cylinders used as emergency make-up for the hydrogen supply system. One of the hydrogen cylinders was broken away from its mounts and moved 10 feet from its original location. The loss of this cylinder severed the manifold tubing, creating a leak path to the atmosphere for the remaining five hydrogen cylinders.

Hydrogen Explosion at Coal-Fired Power Plant

11:23 AM Tue Feb 5, 2008 -- Anonymous (not verified)

An explosion at a coal-fired power plant killed one person and injured 10 others. The blast killed the delivery truck driver who was unloading compressed hydrogen gas, which is used to cool the plant's steam generators. Hydrogen deliveries are routine at the plant, occurring about once a week. Evidence pointed to the premature failure of a pressure-relief device (PRD) rupture disk, which had been repaired by the vendor six months prior to the explosion.

Hydrogen Leak in Auxiliary Building

11:23 AM Wed Jan 10, 2007 -- Anonymous (not verified)

A power plant reported a hydrogen leak inside an auxiliary building. The given plant was in cold shutdown at the time of the event. The discovery of this problem was as a result of an unassociated event involving the activation of a chlorine monitor in the control building. When additional samples indicated no chlorine gas, the shift supervisor ordered further investigation into other plant areas. Because there was no installed detection equipment, portable survey instruments were used to determine gaseous mixtures.