I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen.
Assuming this question relates to the roof of the enclosure, there are no design criteria on this topic to the Panel’s knowledge. The key to the design would be ensure that the exhaust ventilation inlet is located at the highest point and that there are no pockets that can capture hydrogen (restrict flow to the exhaust inlet).
Information on Toyota’s repair garage approach is available…
A best practice, even for small hydrogen vents, is to vent to a dedicated vent system outside the building where possible. Several international codes and standards can be used to provide guidance; the Panel recommends discussing the configuration with a local fire official to ensure their required standards are followed. In the U.S. NFPA 2, Hydrogen Technologies Code, has information in…
It is always recommended that the area in which this work would be done be adequately ventilated and in accordance with the Building Code, NFPA 2 and NFPA 45 if applicable. In the Panel’s opinion, it’s recommended that the weight measuring equipment as you’ve described it be designed for Class 1, Group B, Division 2. Also consult with the local authority having jurisdiction as to the…
While HSP members have limited experience with MFCs in experimental setups, the Panel does not consider them to be reliable to provide a positive flow shutoff. For safety, a shutoff valve in series is recommended. Projects will also need to consider hazardous electrical rating and location when flowing H2. Regarding Coriolis mass flow measuring devices, Coriolis flow meters measure mass rate…
It is difficult to provide trustworthy answers to these questions without understanding the design and configuration of the specific installation. It may be best to consult with a pressure systems expert to evaluate the specific installation and uses. The gas provider may also be a good resource for specifics on gas equipment use. Other beneficial resources include the…
There is limited published research on the effect of water sprays on hydrogen deflagrations and deflagration-to-detonation transition, and more extensive data on water spray effects on hydrocarbon gas explosions. The results show the benefits, where there are benefits, to be highly scenario dependent. For example, Carlson et al. (Atomics International report, 1973) described hydrogen…
The lesson learned (LL) article referenced in the question cites an incident that occurred in December 1969. While there may have been other accidents, the HSP does not have any other LL articles on alkaline water electrolysis explosions. In the LL article that was updated in 2017, the technology described employs a potassium hydroxide (KOH) electrolyte solution. The KOH electrolyte is held by…
No, but it is always necessary to determine the possibility of an adverse chemical reaction with the particular material being used for the mesh.
The Panel has not received such inquiries. Section 14.2 of NFPA 69 Standard for Explosion Prevention Systems covers foam and mesh requirements. NFPA 69 states in 14.3.4 that the tests shall be conducted with a flammable gas/air mixture with a fundamental burning velocity representative of the burning velocities of flammable vapors expected in the intended applications.