1. As of January 2024, we are not aware of any public data on incidents or investigations where a hydrogen fired steam boiler exploded.
2. The potential for detonations within a boiler tube would depend on both the equivalence ratio of the hydrogen present and the diameter of the boiler tube.
a. At a minimum, if the circumference of the tube is…
A design condition for vent stacks is to always assume that the hydrogen will ignite. The stack musts be designed such that it can withstand those conditions as well as minimize radiation to surrounding personnel and exposures. Although hydrogen fires have comparatively low radiation compared to hydrocarbon fuels, the radiation from large releases from vent stacks can be quite high. Documents…
The purity required will be a function of the end use application. There are a variety of grades of hydrogen that can be purchased. The H2 purity will also vary based on source (GH2 or LH2) and production method. CGA G-5.3, Commodity Specification for Hydrogen, lists several typical purities of both liquid and gaseous hydrogen. Standard GH2 available from most suppliers is 99.95% hydrogen.…
Yes, although not as common as high-pressure gas releases, high-velocity cold H2 gas has ignited during rupture disc and relief valve activation.
The water vapor cloud formed from venting cold hydrogen gas from a liquid hydrogen tank will vary in size depending upon atmospheric conditions including ambient temperature and humidity. There is not a direct relationship between the water vapor cloud and the flammable cloud of hydrogen, but it’s often used as a proxy.
Initially upon release, it is possible that H2 vapor from…
Yes, these would be ignitable mixtures. In this case, it does not appear complicated geometry is involved, so 1200 psig pipe should be more than adequate to protect against internal deflagration. The most likely scenario is a "backfire," similar to a car, where ignition occurs too soon and shoots out the open end of the pipe. Consider using an inline deflagration flash arrestor on the…