The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such…

Category: Piping

The Panel considers two approaches to be acceptable. 

  1. Stainless steel (corrosion resistant) lines embedded in concrete. This keeps the piping out of direct contact with the earth and provides a degree of physical protection from activities such as digging.
  2. Lines enclosed within a PVC sleeve. The PVC sleeve would usually be directly buried but could also be embedded in…
Category: Piping

Hydrogen cylinders contain pure hydrogen unless they are specifically manufactured for and marked as a mixture. The purity grade is usually between 99.5% and 99.9999%. The balance is typically inert gases (such as nitrogen) with just ppm levels of other contaminants, but this can vary depending upon the production source. When emptied, the residual is still the same purity of hydrogen, just at…

Category: Storage
Keywords: Storage, Cylinder

This production rate of hydrogen of about 96 kg/h is quite significant, which depending upon the application might require a significant amount of storage. There will be a need to determine how many kg the project wants to store from this production rate in order to determine how much hydrogen ground storage is needed. Since the project is in Europe, look for pressure vessel manufacturers that…

Category: Storage

If liquid hydrogen usage is sufficiently high at the fueling station, there may be no need to vent any boiloff generated from the LH2 storage tank. Boil-off gas should be minimized through system design, but where needed, the boil-off hydrogen along with any other hydrogen released must be vented through a local vent stack which is constructed to safely vent the hydrogen in accordance with CGA…

This can be a complex problem and response to insulation failure should be considered in the emergency response guidelines and procedures. 
First, a tank with an insulation failure may boil off at an elevated rate which applicable codes build into the relief device and vent system design.
Second, ice and oxygen enriched liquefied air can form where inadequately insulated surfaces…

Category: Storage
Keywords: Storage, Oxygen, Leak, Safety, Tank

Double pipes can be used in certain circumstances to reduce the likelihood of external leaks and increase
the likelihood of detection by monitoring the space between the two pipes. Vacuum jacketed piping is
double walled and is used in liquid hydrogen service to provide insulation. While not equipped with gas
detection in the annular space, loss of vacuum is used to indicate an…

Category: Piping

Liquid hydrogen is much less likely to pool than liquified natural gas (LNG) due to its low heat of vaporization. Very large facilities are often equipped with methods to enhance vaporization, such as crushed stone under tanks, as well as diversion systems to allow liquid hydrogen to spill and boil off in a safe area. Care needs to be taken that diversion systems do not create a hazardous…