The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such…

Category: Piping

The Panel considers two approaches to be acceptable. 

  1. Stainless steel (corrosion resistant) lines embedded in concrete. This keeps the piping out of direct contact with the earth and provides a degree of physical protection from activities such as digging.
  2. Lines enclosed within a PVC sleeve. The PVC sleeve would usually be directly buried but could also be embedded in…
Category: Piping

There are no specific code resources that specifically cover hydrogen liquefaction plants, but they must be built to the general building, electrical, machinery, piping, and mechanical codes for process plants. Codes such as NFPA 2, Hydrogen Technologies Code, for installation and emergency response may also be used for reference. It may also be beneficial to break down the requirements into…

Category: System Design

The regulations for electrical classification in Europe and a US jurisdiction such as California are significantly different and should not be assumed to be the same. Consultation with Authorities Having Jurisdiction or a Third- Party expert regarding the application of the US National Electric Code is advised. Some additional important points:


The HSP has concerns with the use of…

Category: System Design

The British Standards Institute (BSI) has published BS ISO 22734:2019, a British nationalized version of the packaged water electrolyzer safety certification standard. This standard can be used by a Notified Body (BSI is one of many operating in the UK and in Europe) to certify electrolyzer safety to established norms for this equipment. This standard addresses safety of containerized hydrogen…

Category: System Design

The vent system for the excess hydrogen should be vented in accordance with NFPA 2 and CGA G-5.4 and G-5.5. The oxygen also must be vented safely and should be in accordance with NFPA and CGA G-4.4. 


Please be extremely cautious with compressing hydrogen. NEC/NFPA 70 and its Articles 500/505 address electrical equipment in flammable atmospheres. Please also consider the…

Category: System Design

Regarding cylinders, it is not necessary to capture the fuse-backed devices which are on the cylinder itself. However, all other relief devices and vent valves must exhaust from a vent system designed in accordance with CGA G-5.5. Also, note that NFPA 2-7.1.17 requires compliance with CGA G-5.5 regardless of storage quantity when the vent system is servicing pressure relief devices. Cylinders…

Category: System Design

Panel members have not encountered a device or area classification for ATEX approval within Canada. ATEX is a European Union directive and is not generally recognized within North American standards. The second link below references a UL similarity. https://news.nilfiskcfm.com/2017/03/atex-certification-applicable-north-america/;    https://www.ul.com/services/atex-certification-…

Category: System Design

NFPA 2 has provisions for the use of LH2, and there are many existing fueling stations that store and use liquid hydrogen. One challenge for the use of LH2 in stations with small footprints is the code required separation distances from exposures. NPFA 2 has updated the separation distances with a risk informed approach in the 2023 edition.


Another possibility for public fuel…

Category: System Design

Double pipes can be used in certain circumstances to reduce the likelihood of external leaks and increase
the likelihood of detection by monitoring the space between the two pipes. Vacuum jacketed piping is
double walled and is used in liquid hydrogen service to provide insulation. While not equipped with gas
detection in the annular space, loss of vacuum is used to indicate an…