A pressure gauge is not usually provided, as one set of devices (safety valve and rupture disc) is always online by design. If the diverter valve connecting the two sets of relief devices is in the center position, both sets are online although depending upon the design of the diverter valve, it might not allow full flow in either direction. For the secondary stack with a rupture disc and a…
As is mentioned in the question, it should always be assumed that vent stack fires will occur. The vent stack must be designed to withstand a possible deflagration and the heat from a continuous vent stack fire. The stack should also have sufficient height and be located such that thermal radiation is safe for surrounding personnel, equipment, and buildings. The codes and standards have…
Refineries and large petrochemical plants will frequently have flare systems for H2 and other flammable materials. One of the major purposes of these flare systems is to prevent a large unignited cloud from forming since that could result in an explosion hazard and large deflagration overpressures if there is a delayed ignition. However, these are in large facilities which have the…
This is a fairly common arrangement and can be acceptable if properly designed. Some considerations:
The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for…
The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…