Hydrogen cylinders contain pure hydrogen unless they are specifically manufactured for and marked as a mixture. The purity grade is usually between 99.5% and 99.9999%. The balance is typically inert gases (such as nitrogen) with just ppm levels of other contaminants, but this can vary depending upon the production source. When emptied, the residual is still the same purity of hydrogen, just at…

Category: Storage
Keywords: Storage, Cylinder

This production rate of hydrogen of about 96 kg/h is quite significant, which depending upon the application might require a significant amount of storage. There will be a need to determine how many kg the project wants to store from this production rate in order to determine how much hydrogen ground storage is needed. Since the project is in Europe, look for pressure vessel manufacturers that…

Category: Storage

This can be a complex problem and response to insulation failure should be considered in the emergency response guidelines and procedures. 
First, a tank with an insulation failure may boil off at an elevated rate which applicable codes build into the relief device and vent system design.
Second, ice and oxygen enriched liquefied air can form where inadequately insulated surfaces…

Category: Storage
Keywords: Storage, Oxygen, Leak, Safety, Tank

Liquid hydrogen is much less likely to pool than liquified natural gas (LNG) due to its low heat of vaporization. Very large facilities are often equipped with methods to enhance vaporization, such as crushed stone under tanks, as well as diversion systems to allow liquid hydrogen to spill and boil off in a safe area. Care needs to be taken that diversion systems do not create a hazardous…

Category: Storage

By definition, liquid hydrogen can BLEVE, but this is highly unlikely. Liquid hydrogen is stored in a double wall tank with vacuum insulation. This protects the primary pressure vessel from direct impingement and the very cold liquid provides self-cooling of the vessel walls. Tanks are also equipped with redundant pressure relief systems that are sized for fire exposure.

Category: Storage

Flammable hydrogen releases can result in deflagration and transition to a detonation. Whether the
deflagration transitions to a detonation depends on numerous parameters such as cloud size, hydrogen
concentration, confinement, and congestion. Releases into confined or congested areas are more
susceptible to generating significant deflagration over-pressures and more likely to…

Underground storage tanks can be either installed in a vault or directly buried. Both offer additional
protection from external impact and fire, but each has unique challenges. Vaults must be properly
ventilated and designed to not create an explosion or asphyxiation risk. Direct burial vessels should not
have any underground leak points and must be protected from corrosion. Both…

Category: Storage

There are numerous models that can be used to assess the consequence and risk of leaks and releases.
One such model is HYRAM which is publicly available from Sandia and the US DOE.