Explosion in condenser area two hours after the unit tripped (due to a stator earth fault). The stator earth fault had damaged two hydrogen cooler tubes, which allowed hydrogen to pass from the…
There was a massive explosion at one of the generator-turbine units of a coal-based power station. Undetected hydrogen leak from the generator was identified as a major trigger.According to the news…
Leak from faulty hydrogen seal ignited by short circuit between inboard slip ring and outboard slip ring radial lead connection. Hydrogen flame caused damage to brush gear assembly and inboard slip…
A short circuit occurred in a bus bar system in a transformer building, causing a fire in adjacent switches. This was followed by the tripping out of the three refinery turbo-alternators, cutting off…
Maintenance works were ongoing after an outage at a turbine and generator unit of the plant. Fifteen maintenance mechanics were working at that time on the unit. An access cover was removed causing…
Ejection of rotor wedge material lead to vibration induced failure of components, including hydrogen seals. Serious fire resulted from hydrogen leakage, which subsequently lead to an oil fire.…