Skip to main content

Failure of an Argon Check Valve

Severity
Near-Miss
Was Hydrogen Released?
Yes
Was There Ignition?
No
Incident Date
Incident Attributes
Setting
Equipment
Damage and Injuries
Probable Cause
Contributing Factors
When Incident Was Discovered
Describe the incident, including corrective steps taken and their result.

A facility replaced the copper tubing used for hydrogen distribution, with stainless steel tubing. This was done to address a fire protection concern related to the solder on the copper tubing being susceptible to heat, melting, and releasing a flammable gas. The facility maintenance personnel completed the replacement, noted the pressure on the hydrogen bottle, and left the building. When the maintenance person returned on the following day, s/he noticed the pressure on the hydrogen bottle had dropped 500 psi overnight, indicating a leak in the system. S/he notified the appropriate facility personnel and together they began to determine why the hydrogen had dropped 500 psi overnight. The hydrogen line originates at a manifold, which is part of a glove box atmosphere purification system that also includes an argon line. The onsite personnel experimented with the valves associated with the hydrogen and argon lines and determined that the check valve associated with the argon line was defective. As a result, the hydrogen was back flowing through the argon check valve into the argon supply line.

The direct cause of this occurrence was attributed to a failed argon check valve that allowed hydrogen to escape from the hydrogen supply manifold and enter the argon system. The contributing and root cause was identified as a design problem. The check valve installed to prevent the back flow of hydrogen into the argon system, designed to open with an upstream pressure of 1/3 psig. The product catalog states that valves with nominal cracking pressure of 8 psig or lower may require back pressure to reseal bubble-tight. The back pressure in the system was not sufficient to reseal a 1/3 psig valve. Product data suggests that a the valve, having a cracking pressure of 10 psig and not requiring back pressure to reseal, should have been chosen for this application. Also, double check valves (i.e., two check valves in series) should have been installed to provide double isolation between the two gas systems. However, it is doubtful in this case if two valves would have been adequate to prevent the backflow of hydrogen since the wrong sized valve (i.e., 1/3 psi) was initially chosen.

The hydrogen was sufficiently diluted with argon in the argon system and did not pose a safety, fire, or explosion hazard.

Lessons Learned

This occurrence underscores the importance of appropriate design, equipment selection, and design review; the potential drawbacks of sharing utilities with other facilities; and the need to simplify [in this case, glove box atmosphere purification equipment/process] operations as much as possible.

Key:

  • = No Ignition
  • = Explosion
  • = Fire
Hydrogen Incident Summaries by Equipment and Primary Cause/Issue
Equipment / CauseEquipment Design or SelectionComponent FailureOperational ErrorInstallation or MaintenanceInadequate Gas or Flame DetectionEmergency Shutdown ResponseOther or Unknown
Hydrogen Gas Metal Cylinder or Regulator 3/31/2012
4/30/1995
2/6/2013
4/26/201012/31/1969  3/17/1999
11/1/2001
12/23/2003
Piping/Valves4/4/2002
2/2/2008
5/11/1999
4/20/1987
11/4/1997
12/31/1969
8/19/1986
7/27/1991
12/19/2004
2/6/2008
10/3/2008
4/5/2006
5/1/2007
9/19/2007
10/31/1980
2/7/20091/24/1999
2/24/2006
6/8/1998
12/31/1969
2/7/2009
9/1/1992
10/31/1980
10/3/2008 
Tubing/Fittings/Hose 9/23/1999
8/2/2004
8/6/2008
9/19/2007
1/1/19829/30/2004
10/7/2005
 10/7/2005 
Compressor 10/5/2009
6/10/2007
8/21/2008
1/15/2019
  10/5/20098/21/2008 
Liquid Hydrogen Tank or Delivery Truck4/27/198912/19/2004
1/19/2009
8/6/200412/31/1969 1/1/197412/17/2004
Pressure Relief Device7/25/2013
5/4/2012
1/15/2002
1/08/2007
12/31/1969    
Instrument1/15/20193/17/1999
12/31/1969
2/6/2013
  11/13/73  
Hydrogen Generation Equipment7/27/1999  10/23/2001   
Vehicle or Lift Truck 7/21/2011    2/8/2011
12/9/2010
Fuel Dispenser 8/2/2004
5/1/2007
6/11/2007
9/19/2007
 2/24/2006
1/22/2009
   
Fuel Cell Stack      5/3/2004
12/9/2010
2/8/2011
Hydrogen Cooled Generator   12/31/1969
2/7/2009
   
Other (floor drain, lab
anaerobic chamber,
heated glassware,
test chamber,
gaseous hydrogen
composite cylinder,
delivery truck)
 11/14/1994
7/21/2011
7/27/1999
6/28/2010
8/21/2008
12/31/1969
3/22/2018
  6/10/2019
  • = No Ignition
  • = Explosion
  • = Fire
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.

Contact info

We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.

Recent Posts